Skip to main content

D 21 FOX

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
18.30
kVA
Continuous power (PRP)
14.64
kW
Emergency power (E.P.)
20.10
kVA
Emergency power (E.P.)
16.08
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 50 Hz
Voltage (V) 380 VAC

DIMENSIONS AND NOISE

Width 945 mm
Length 2030 mm
Height 1340 mm
Weight 820 kg
Sound pressure 7 m. 65.0 dBA

AWESOME FEATURES

1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model D 21 FOX
Connection Series star
DIMENSIONS AND NOISE
Width 945 mm
Length 2030 mm
Height 1340 mm
Weight 820 kg
Sound pressure 7 m. 65.0 dBA
ENGINE BASE DATA
Description DEUTZ
Engine model F3M2011
P.R.P. Power 20.2 kVA
E.P. Power 21.3 kVA
Cylinders 3.0
Speed 1500.0 r.p.m.
Cubic capacity 2.3 l
Air intake Aspirated
Standard voltage 12.0 Vdc
Optional voltage 24.0 Vdc
Sae 3-11½
BMEP 690.0 kPa
Cooling Oil
Fuel Cons. at 100% (E.P.) 5.6 l/h
Fuel Cons. at 100% (P.R.P) 5.3 l/h
Fuel Cons. at 75% (P.R.P.) 4.0 l/h
Fuel Cons. at 50% (P.R.P.) 3.1 l/h
Fuel Cons. at 25% (P.R.P.) 2.5 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Stage 2
SPEED REGULATION
Electronic regulator On request
Precision class G2
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 8.5 l
Engine Antifreeze capacity 0.0 l
Radiator antifreeze capacity 0.0 l
Total amount of antifreeze 0 l
HEAT FROM ENGINE
Heat from radiator 11.3 kW
Heat from exhaust 18.1 kW
Heat from radiation 0.0 kW
HEAT FROM EXHAUST
Exhaust temperature 540.0 °C
Combustion air flow 0.0 m³/min
Exhaust gas flow 4.2 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model S0L2-G
E.P. Power 20.1 kVA
P.R.P. Power 18.3 kVA
ALTERNATOR WIRINGS
Connection Series star
Phases 3F+N
Winding 12 terminals Winding 311
Terminal Number 12 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator AS540
Precision 1.0 ± %
RADIATOR
Radiator antifreeze capacity 0.0 l
BASEFRAME DATA
Model FOX
Standard tank 90 l
CANOPY DATA
Canopy model FOX
Silencer model F50/03
Silencer outlet diameter 50.0 mm

STANDARD CONTROL PANEL

Advanced single gen-set controller for stand-by and prime power applications. Direct communication with EFI engines, total remote monitoring and control, easy to install, configure and use, wide range of communication capabilities including: connection via RS232, RS485, CAN and on board USB, internet access using Ethernet, GPRS or 4G support for Modbus and SNMP protocols. Internal PLC support with PLC editor and monitor included in LiteEdit, cloud-based monitoring and control via Onis Visa WebSupervisor, active SMS and emails in different languages, SNMP traps, geofencing and tracking via Onis Visa WebSupervisor, 2x 10 A binary outputs for cranking and fuel solenoid, option for up to 16 additional binary inputs/outputs, flexible event based history with up to 350 events, load shedding, dummy load capability, tier 4 final support, automatic temperature based cooling/heating, comprehensive gen-set protections, multipurpose flexible timers, true RMS measurement.
CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS is a new line of changeover switch panels developed and manufactured by Visa S.P.A. in accordance with CEI EN 61439-2 (construction standard). Specifically used for generating sets, the changeover switch panel allows the changeover between mains/genset or genset/genset. The main part of the panel contains two interlocking contactors or a motorised circuit breaker. All of the parts are installed inside a sturdy powder-coated metal box (RAL7035) and equipped with a lock to close the access door.
ATS PANEL DATA
Description ATS-C 45

user icon menu

USER MENU

User not logged in