Skip to main content

C 1250 S

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
1420.00
kVA
Continuous power (PRP)
1136.00
kW
Emergency power (E.P.)
1600.00
kVA
Emergency power (E.P.)
1280.00
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 60 Hz
Voltage (V) 460 VAC

DIMENSIONS AND NOISE

Width 2200 mm
Length 8600 mm
Height 3400 mm
Weight 14870 kg
Sound pressure 7 m. 79.0 dBA

AWESOME FEATURES

1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model C 1250 S
Connection Star
DIMENSIONS AND NOISE
Width 2200 mm
Length 8600 mm
Height 3400 mm
Weight 14870 kg
Sound pressure 7 m. 79.0 dBA
ENGINE BASE DATA
Description CUMMINS
Engine model KTA50-G3
P.R.P. Power 1420.0 kVA
E.P. Power 1600.0 kVA
Cylinders 16.0
Speed 1800.0 r.p.m.
Cubic capacity 50.3 l
Air intake Turbocharged
Standard voltage 24.0 Vdc
Optional voltage Vdc
Sae 0-18
BMEP 1620.0 kPa
Cooling Water
Fuel Cons. at 100% (E.P.) 330.0 l/h
Fuel Cons. at 100% (P.R.P) 291.0 l/h
Fuel Cons. at 75% (P.R.P.) 222.0 l/h
Fuel Cons. at 50% (P.R.P.) 157.0 l/h
Fuel Cons. at 25% (P.R.P.) 89.0 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Not available
SPEED REGULATION
Electronic regulator Standard
Precision class G3
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 177.0 l
Engine Antifreeze capacity 161.0 l
Radiator antifreeze capacity 152.0 l
Total amount of antifreeze 313 l
HEAT FROM ENGINE
Heat from radiator 900.0 kW
Heat from exhaust 935.0 kW
Heat from radiation 150.0 kW
HEAT FROM EXHAUST
Exhaust temperature 176.0 °C
Combustion air flow 110.4 m³/min
Exhaust gas flow 257.7 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model PI734A
E.P. Power 1615.0 kVA
P.R.P. Power 1510.0 kVA
ALTERNATOR WIRINGS
Connection Star
Phases 3F+N
Winding 6 terminals winding 312
Terminal Number 6 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator MX341
Precision 1.0 ± %
RADIATOR
Radiator antifreeze capacity 152.0 l
BASEFRAME DATA
Model ST60
Standard tank 0 l
CANOPY DATA
Canopy model C60/05/01
Silencer model MSR/a 200
Silencer outlet diameter 219.0 mm

STANDARD CONTROL PANEL

Advanced single gen-set controller for stand-by and prime power applications. Direct communication with EFI engines, total remote monitoring and control, easy to install, configure and use, wide range of communication capabilities including: connection via RS232, RS485, CAN and on board USB, internet access using Ethernet, GPRS or 4G support for Modbus and SNMP protocols. Internal PLC support with PLC editor and monitor included in LiteEdit, cloud-based monitoring and control via Onis Visa WebSupervisor, active SMS and emails in different languages, SNMP traps, geofencing and tracking via Onis Visa WebSupervisor, 2x 10 A binary outputs for cranking and fuel solenoid, option for up to 16 additional binary inputs/outputs, flexible event based history with up to 350 events, load shedding, dummy load capability, tier 4 final support, automatic temperature based cooling/heating, comprehensive gen-set protections, multipurpose flexible timers, true RMS measurement.
CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS PANEL DATA

user icon menu