Skip to main content

F 170 CK

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
195.00
kVA
Continuous power (PRP)
156.00
kW
Emergency power (E.P.)
215.00
kVA
Emergency power (E.P.)
172.00
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 60 Hz
Voltage (V) 208 VAC

DIMENSIONS AND NOISE

Width 1150 mm
Length 2944 mm
Height 1870 mm
Weight 1860 kg
Sound pressure 7 m. 81.0 dBA

AWESOME FEATURES

1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model F 170 CK
Connection Parallel star
DIMENSIONS AND NOISE
Width 1150 mm
Length 2944 mm
Height 1870 mm
Weight 1860 kg
Sound pressure 7 m. 81.0 dBA
ENGINE BASE DATA
Description FPT IVECO
Engine model N67TM4
P.R.P. Power 195.0 kVA
E.P. Power 215.0 kVA
Cylinders 6.0
Speed 1800.0 r.p.m.
Cubic capacity 6.7 l
Air intake Turbocharged
Standard voltage 12.0 Vdc
Optional voltage 24.0 Vdc
Sae 3-11½
BMEP 0.0 kPa
Cooling Water
Fuel Cons. at 100% (E.P.) 0.0 l/h
Fuel Cons. at 100% (P.R.P) 0.0 l/h
Fuel Cons. at 75% (P.R.P.) 0.0 l/h
Fuel Cons. at 50% (P.R.P.) 0.0 l/h
Fuel Cons. at 25% (P.R.P.) 0.0 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Not available
SPEED REGULATION
Electronic regulator On request
Precision class G2
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 17.2 l
Engine Antifreeze capacity 10.5 l
Radiator antifreeze capacity 15.0 l
Total amount of antifreeze 25.5 l
HEAT FROM ENGINE
Heat from radiator 0.0 kW
Heat from exhaust 0.0 kW
Heat from radiation 0.0 kW
HEAT FROM EXHAUST
Exhaust temperature 0.0 °C
Combustion air flow 0.0 m³/min
Exhaust gas flow 26.5 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model UCI274G
E.P. Power 218.5 kVA
P.R.P. Power 205.0 kVA
ALTERNATOR WIRINGS
Connection Parallel star
Phases 3F+N
Winding 12 terminals Winding 311
Terminal Number 12 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator AS440
Precision 1.0 ± %
RADIATOR
Radiator antifreeze capacity 15.0 l
BASEFRAME DATA
Model CK40
Standard tank 280 l
CANOPY DATA
Canopy model CK40
Silencer model MSR/a 80
Silencer outlet diameter 89.0 mm

STANDARD CONTROL PANEL

The DSE4520 MKII Auto Mains (Utility) Failure Control Module is suitable for a wide variety of single gen-set applications.  Whilst maintaining functions included within higher end controllers, such as generator or load power monitoring, the DSE4520 MKII range of especially compact controllers provide the user with the ultimate size to feature ratio.  Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, power and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated on the largest back-lit LCD icon display in its class via an array of warning, electrical trip and shutdown alarms. With a number of flexible inputs, outputs and protections, the module can be easily adapted to suit a wide range of applications.  Through USB Communication the module can be easily configured using the DSE Configuration Suite PC Software or can be fully configured through the module’s front panel editor.
CONTROL PANEL DATA
Description DSE4520

CONTROL PANEL DATASHEETS

STANDARD ATS

ATS PANEL DATA

user icon menu

USER MENU

User not logged in