Skip to main content

P 252 B

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
225.00
kVA
Continuous power (PRP)
180.00
kW
Emergency power (E.P.)
250.00
kVA
Emergency power (E.P.)
200.00
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 60 Hz
Voltage (V) 440 VAC

DIMENSIONS AND NOISE

Width 1120 mm
Length 2430 mm
Height 2000 mm
Weight 1850 kg

AWESOME FEATURES

1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Large capacity steel baseframe-fuel tank with level sensor
4- Industrial silencer and coupling flange
5- Electrical panel mounted on board the unit with digital control device installed in metal box
6- Compact for easy handling and use
7- Test report, manuals and electrical drawings supplied
8- World wide after sales service and technical support
Further details on the technical data sheet

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model P 252 B
Connection Series star
DIMENSIONS AND NOISE
Width 1120 mm
Length 2430 mm
Height 2000 mm
Weight 1850 kg
ENGINE BASE DATA
Description PERKINS
Engine model 1206A-E70TTAG3
P.R.P. Power 225.0 kVA
E.P. Power 250.0 kVA
Cylinders 6.0
Speed 1800.0 r.p.m.
Cubic capacity 7.0 l
Air intake Turbocharged
Standard voltage 12.0 Vdc
Optional voltage Vdc
Sae 2-11½
BMEP 2064.0 kPa
Cooling Water
Fuel Cons. at 100% (E.P.) 61.1 l/h
Fuel Cons. at 100% (P.R.P) 54.5 l/h
Fuel Cons. at 75% (P.R.P.) 40.4 l/h
Fuel Cons. at 50% (P.R.P.) 27.8 l/h
Fuel Cons. at 25% (P.R.P.) 16.5 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Not available
SPEED REGULATION
Electronic regulator Standard
Precision class G2
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 16.0 l
Engine Antifreeze capacity 13.7 l
Radiator antifreeze capacity 11.3 l
Total amount of antifreeze 25 l
HEAT FROM ENGINE
Heat from radiator 182.7 kW
Heat from exhaust 246.3 kW
Heat from radiation 0.0 kW
HEAT FROM EXHAUST
Exhaust temperature 505.0 °C
Combustion air flow 14.0 m³/min
Exhaust gas flow 31.2 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model UCI274H
E.P. Power 265.0 kVA
P.R.P. Power 245.0 kVA
ALTERNATOR WIRINGS
Connection Series star
Phases 3F+N
Winding 12 terminals Winding 311
Terminal Number 12 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator AS440
Precision 1.0 ± %
RADIATOR
Radiator antifreeze capacity 11.3 l
BASEFRAME DATA
Model T2
Standard tank 520 l
CANOPY DATA
Canopy model SENZA COFANO
Silencer model MS 25
Silencer outlet diameter 114.0 mm

STANDARD CONTROL PANEL

Advanced single gen-set controller for stand-by and prime power applications. Direct communication with EFI engines, total remote monitoring and control, easy to install, configure and use, wide range of communication capabilities including: connection via RS232, RS485, CAN and on board USB, internet access using Ethernet, GPRS or 4G support for Modbus and SNMP protocols. Internal PLC support with PLC editor and monitor included in LiteEdit, cloud-based monitoring and control via Onis Visa WebSupervisor, active SMS and emails in different languages, SNMP traps, geofencing and tracking via Onis Visa WebSupervisor, 2x 10 A binary outputs for cranking and fuel solenoid, option for up to 16 additional binary inputs/outputs, flexible event based history with up to 350 events, load shedding, dummy load capability, tier 4 final support, automatic temperature based cooling/heating, comprehensive gen-set protections, multipurpose flexible timers, true RMS measurement.
CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS PANEL DATA
Description ATS-M 315

user icon menu

USER MENU