Skip to main content

DS 745 GX

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
840.00
kVA
Continuous power (PRP)
672.00
kW
Emergency power (E.P.)
930.00
kVA
Emergency power (E.P.)
744.00
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 60 Hz
Voltage (V) 208 VAC

DIMENSIONS AND NOISE

Width 1860 mm
Length 5020 mm
Height 2570 mm
Weight 5820 kg

AWESOME FEATURES

1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model DS 745 GX
Connection Parallel star
DIMENSIONS AND NOISE
Width 1860 mm
Length 5020 mm
Height 2570 mm
Weight 5820 kg
ENGINE BASE DATA
Description HYUNDAI(DOOSAN)
Engine model DP222LCF
P.R.P. Power 840.0 kVA
E.P. Power 930.0 kVA
Cylinders 12.0
Speed 1800.0 r.p.m.
Cubic capacity 21.9 l
Air intake Turbocharged
Standard voltage 24.0 Vdc
Optional voltage Vdc
Sae 1-14
BMEP 2290.0 kPa
Cooling Water
Fuel Cons. at 100% (E.P.) 203.8 l/h
Fuel Cons. at 100% (P.R.P) 183.2 l/h
Fuel Cons. at 75% (P.R.P.) 134.4 l/h
Fuel Cons. at 50% (P.R.P.) 91.3 l/h
Fuel Cons. at 25% (P.R.P.) 49.1 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Not available
SPEED REGULATION
Electronic regulator Standard
Precision class G3
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 42.0 l
Engine Antifreeze capacity 23.0 l
Radiator antifreeze capacity 91.0 l
Total amount of antifreeze 114 l
HEAT FROM ENGINE
Heat from radiator 479.0 kW
Heat from exhaust 718.0 kW
Heat from radiation 73.0 kW
HEAT FROM EXHAUST
Exhaust temperature 493.0 °C
Combustion air flow 58.6 m³/min
Exhaust gas flow 130.0 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model S6L1D-C
E.P. Power 950.0 kVA
P.R.P. Power 875.0 kVA
ALTERNATOR WIRINGS
Connection Parallel star
Phases 3F+N
Winding 12 terminals Winding 311
Terminal Number 12 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator MX322
Precision 0.5 ± %
RADIATOR
Radiator antifreeze capacity 91.0 l
BASEFRAME DATA
Model GV201
Standard tank 950 l
CANOPY DATA
Canopy model GV201
Silencer model MSR/a 150
Silencer outlet diameter 168.0 mm

STANDARD CONTROL PANEL

Advanced single gen-set controller for stand-by and prime power applications. Direct communication with EFI engines, total remote monitoring and control, easy to install, configure and use, wide range of communication capabilities including: connection via RS232, RS485, CAN and on board USB, internet access using Ethernet, GPRS or 4G support for Modbus and SNMP protocols. Internal PLC support with PLC editor and monitor included in LiteEdit, cloud-based monitoring and control via Onis Visa WebSupervisor, active SMS and emails in different languages, SNMP traps, geofencing and tracking via Onis Visa WebSupervisor, 2x 10 A binary outputs for cranking and fuel solenoid, option for up to 16 additional binary inputs/outputs, flexible event based history with up to 350 events, load shedding, dummy load capability, tier 4 final support, automatic temperature based cooling/heating, comprehensive gen-set protections, multipurpose flexible timers, true RMS measurement.
CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS PANEL DATA

user icon menu

USER MENU

User not logged in