Skip to main content

BD 800 GX

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
810.00
kVA
Continuous power (PRP)
648.00
kW
Emergency power (E.P.)
860.00
kVA
Emergency power (E.P.)
688.00
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 50 Hz
Voltage (V) 400 VAC

DIMENSIONS AND NOISE

Width 1940 mm
Length 5800 mm
Height 2550 mm
Weight 8650 kg
Sound pressure 7 m. 72.0 dBA

AWESOME FEATURES

1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model BD 800 GX
Connection Star
DIMENSIONS AND NOISE
Width 1940 mm
Length 5800 mm
Height 2550 mm
Weight 8650 kg
Sound pressure 7 m. 72.0 dBA
ENGINE BASE DATA
Description BAUDOUIN
Engine model 12M26G900/5
P.R.P. Power 815.0 kVA
E.P. Power 900.0 kVA
Cylinders 12.0
Speed 1500.0 r.p.m.
Cubic capacity 31.8 l
Air intake Turbocharged
Standard voltage 24.0 Vdc
Optional voltage Vdc
Sae 0-18
BMEP 1995.0 kPa
Cooling Water
Fuel Cons. at 100% (E.P.) 190.5 l/h
Fuel Cons. at 100% (P.R.P) 172.5 l/h
Fuel Cons. at 75% (P.R.P.) 130.4 l/h
Fuel Cons. at 50% (P.R.P.) 91.0 l/h
Fuel Cons. at 25% (P.R.P.) 51.9 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Not available
SPEED REGULATION
Electronic regulator Standard
Precision class G3
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 114.0 l
Engine Antifreeze capacity 83.0 l
Radiator antifreeze capacity 0.0 l
Total amount of antifreeze 83 l
HEAT FROM ENGINE
Heat from radiator 1066.0 kW
Heat from exhaust 0.0 kW
Heat from radiation 0.0 kW
HEAT FROM EXHAUST
Exhaust temperature 550.0 °C
Combustion air flow 60.9 m³/min
Exhaust gas flow 207.1 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model S6L1D-C
E.P. Power 860.0 kVA
P.R.P. Power 810.0 kVA
ALTERNATOR WIRINGS
Connection Star
Phases 3F+N
Winding 6 terminals winding 312
Terminal Number 6 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator MX322
Precision 0.5 ± %
RADIATOR
Radiator antifreeze capacity 0.0 l
BASEFRAME DATA
Model GV300
Standard tank 400 l
CANOPY DATA
Canopy model GV300
Silencer model MSR/A 250
Silencer outlet diameter 273.0 mm

STANDARD CONTROL PANEL

Advanced single gen-set controller for stand-by and prime power applications. Direct communication with EFI engines, total remote monitoring and control, easy to install, configure and use, wide range of communication capabilities including: connection via RS232, RS485, CAN and on board USB, internet access using Ethernet, GPRS or 4G support for Modbus and SNMP protocols. Internal PLC support with PLC editor and monitor included in LiteEdit, cloud-based monitoring and control via Onis Visa WebSupervisor, active SMS and emails in different languages, SNMP traps, geofencing and tracking via Onis Visa WebSupervisor, 2x 10 A binary outputs for cranking and fuel solenoid, option for up to 16 additional binary inputs/outputs, flexible event based history with up to 350 events, load shedding, dummy load capability, tier 4 final support, automatic temperature based cooling/heating, comprehensive gen-set protections, multipurpose flexible timers, true RMS measurement.
CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS PANEL DATA
Description ATS-M 1250

user icon menu

USER MENU

User not logged in