BD 30 CK
DATASHEET PDF
NEED MORE INFO?
MAIN DATA
Continuous power (PRP) |
30.00
|
kVA |
Continuous power (PRP) |
24.00
|
kW |
Emergency power (E.P.) |
33.00
|
kVA |
Emergency power (E.P.) |
26.40
|
kW |
Power factor | 0.8 | cos(fi) |
Frequency (Hz) | 50 | Hz |
Voltage (V) | 400 | VAC |
DIMENSIONS AND NOISE
AWESOME FEATURES
1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
2- Industrial brushless alternator with AVR
3- Steel baseframe, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
TECHNICAL DATA
GEN SET GENERAL DATA | ||
---|---|---|
Genset model | BD 30 CK | |
Connection | Series star |
DIMENSIONS AND NOISE |
---|
ENGINE BASE DATA | ||
---|---|---|
Description | BAUDOUIN | |
Engine model | 4M06G44/5 | |
P.R.P. Power | 40.0 | kVA |
E.P. Power | 44.0 | kVA |
Cylinders | 4.0 | |
Speed | 1500.0 | r.p.m. |
Cubic capacity | 2.3 | l |
Air intake | Turbocharged | |
Standard voltage | 12.0 | Vdc |
Optional voltage | Vdc | |
Sae | 3-11½ | |
BMEP | 1391.0 | kPa |
Cooling | Water | |
Fuel Cons. at 100% (E.P.) | 10.8 | l/h |
Fuel Cons. at 100% (P.R.P) | 9.5 | l/h |
Fuel Cons. at 75% (P.R.P.) | 7.0 | l/h |
Fuel Cons. at 50% (P.R.P.) | 4.7 | l/h |
Fuel Cons. at 25% (P.R.P.) | 2.8 | l/h |
EMISSIONS | ||
---|---|---|
TA Luft | Not available | |
TA Luft/2 | Not available | |
EPA | Not available | |
Stage | Not available |
SPEED REGULATION | ||
---|---|---|
Electronic regulator | Standard | |
Precision class | G3 |
ENGINE DIMENSIONS AND LIQUIDS | ||
---|---|---|
Oil quantity | 11.5 | l |
Engine Antifreeze capacity | 5.0 | l |
Radiator antifreeze capacity | 11.0 | l |
Total amount of antifreeze | 16 | l |
HEAT FROM ENGINE | ||
---|---|---|
Heat from radiator | 59.9 | kW |
Heat from exhaust | 0.0 | kW |
Heat from radiation | 0.0 | kW |
HEAT FROM EXHAUST | ||
---|---|---|
Exhaust temperature | 650.0 | °C |
Combustion air flow | 2.2 | m³/min |
Exhaust gas flow | 7.9 | m³/min |
GENERAL ALTERNATOR DATA | ||
---|---|---|
Description | STAMFORD | |
Alternator model | S0L2-P | |
E.P. Power | 33.0 | kVA |
P.R.P. Power | 30.0 | kVA |
ALTERNATOR WIRINGS | ||
---|---|---|
Connection | Series star | |
Phases | 3F+N | |
Winding | 12 terminals Winding 311 | |
Terminal Number | 12 | nr. |
ALTERNATOR PROTECTION | ||
---|---|---|
IP Protection | 23 |
ALTERNATOR REGULATOR | ||
---|---|---|
Electronic regulator | AS540 | |
Precision | 1.0 | ± % |
RADIATOR | ||
---|---|---|
Radiator antifreeze capacity | 11.0 | l |
BASEFRAME DATA | ||
---|---|---|
Model | CK20 | |
Standard tank | 90 | l |
CANOPY DATA | ||
---|---|---|
Canopy model | CK20 | |
Silencer model | F60/00 | |
Silencer outlet diameter | 60.0 | mm |
STANDARD CONTROL PANEL
The DSE4520 MKII Auto Mains (Utility) Failure Control Module is suitable for a wide variety of single gen-set applications. Whilst maintaining functions included within higher end controllers, such as generator or load power monitoring, the DSE4520 MKII range of especially compact controllers provide the user with the ultimate size to feature ratio. Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, power and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated on the largest back-lit LCD icon display in its class via an array of warning, electrical trip and shutdown alarms. With a number of flexible inputs, outputs and protections, the module can be easily adapted to suit a wide range of applications. Through USB Communication the module can be easily configured using the DSE Configuration Suite PC Software or can be fully configured through the module’s front panel editor.
CONTROL PANEL DATA | ||
---|---|---|
Description | DSE4520 |
CONTROL PANEL DATASHEETS
STANDARD ATS
ATS is a new line of changeover switch panels developed and manufactured by Visa S.P.A. in accordance with CEI EN 61439-2 (construction standard). Specifically used for generating sets, the changeover switch panel allows the changeover between mains/genset or genset/genset. The main part of the panel contains two interlocking contactors or a motorised circuit breaker. All of the parts are installed inside a sturdy powder-coated metal box (RAL7035) and equipped with a lock to close the access door.
ATS PANEL DATA | ||
---|---|---|
Description | ATS-C 45 |